🔧 Room Dimensions & Details
❄️ Required Cooling Load
Based on standard manual J approximations
0
Total BTUs / Hour
0.0
AC Tonnage (Tons)
0.0
Capacity (kW)
Ideal AC Size: Loading...
⚡ HVAC Energy Savings Calculator
Older non-inverter units are typically 10-12 SEER.
Modern inverter ACs range from 16-24 SEER.
💰 Expected Savings
Estimated annual comparison
Old Unit Cost / Yr
₹ 0
New Unit Cost / Yr
₹ 0
Annual Savings
₹ 0
0% reduction in cooling costs
Over 10 years, you save ₹ 0!
💨 Duct Sizing & Airflow Calculator
Cubic Feet per Minute of air.
Feet per Minute. Residential trunks usually 700-900 FPM.
We will calculate the required width to match this height.
📐 Recommended Dimensions
Based on Velocity Method sizing
160.0
Cross-Sectional Area (Sq. In)
14.3"
Round Duct Diameter
20.0"
Required Width (Rectangular)
Standard Size: 20" x 8" or 14" Round
🧪 Superheat Diagnostic Tool
TXVs normally maintain a fixed superheat (~10-15°F).
Taken at the return grille.
Taken at the condenser coil.
Measured physically on the large copper pipe.
Read from vapor (low-side) gauge scale.
📊 Charge Diagnostics
Compare Target vs. Actual Superheat
11.5°F
Target Superheat
15.0°F
Actual Superheat
⚠️
ADD REFRIGERANT
Actual superheat is too high. System is undercharged.
Tolerance is generally Target ± 3°F. Ensure system has been running for 15+ minutes before testing.
⚙️ Fan & Pump Affinity Laws
📈 Projected Performance
Based on proportional, square, and cube laws
2,500
New Flow Rate (Q2)
Law 1: Flow changes directly with speed
2.34
New Pressure (P2)
Law 2: Pressure via square of speed
3.91
New Power (HP2)
Law 3: Power via cube of speed
⚠️ Warning: Motor horsepower required increases radically. Ensure the motor is rated for the new HP.
☁️ Digital Psychrometric Tool
Used to approximate atmospheric pressure. Sea Level = 0ft.
🧪 Thermodynamic State
Calculated using strict empirical formulas
62.5°F
Wet Bulb Temp
55.0°F
Dew Point
28.1
Enthalpy (BTU/lb)
65.0
Moisture (Grains/lb)
Formula Note: Uses Magnus-Tetens approximation and Stull equation for wet-bulb. Accurate within ±0.5% for standard HVAC ranges.
PHARMA & CLEAN ROOM FOCUSED
🏥 ISO Cleanroom ACH Calculator
60 - 90
Required Air Changes (ACH)
2,700
Room Volume (Cu.Ft)
2,700 - 4,050
Required Airflow (CFM)
GMP Guidelines recommend minimum airflow ranges based on operational status (at-rest vs in-operation). Values are conservative rules of thumb.
🌬️ Room Pressurization (Cascade)
Standard GMP cascade is 10-15 Pa (0.04 - 0.06 in. w.c.)
Total area of door undercuts, pass-through cracks, etc. (E.g. a 3ft door with 1/2" gap = 18 sq in).
81
Required Airflow Offset (CFM)
SUPPLY EXCESS: You must supply 81 CFM more than you return/exhaust.
Equation used: Q = 2610 × A × √ΔP. This calculates required offset to "inflate" or "deflate" the room against leakage.
🔲 HEPA Terminal Velocity
Face area excludes the mechanical frame.
GMP standard for UDAF is 90 FPM ± 20% (72-108 FPM).
5
Filters Required
77
Actual Velocity (FPM)
✅ FACE VELOCITY PASSES VALIDATION (Within 72-108 FPM)
💧 Internal Vapor Load Generator
Light manufacturing = approx. 1050 grains/hr per person.
Moisture off-gassing from open tanks, drying trays, washing stations.
7.7
Total Water Vapor load (LBS / HR)
53,900
Grains per Hour
Use these values to size Desiccant Wheels or deep-cooling coils. Note: This isolates internal loads only (excludes fresh air / envelope infiltration).
⏱️ Cleanroom Recovery Time
Standard GMP clean-down requires the room to recover within 15-20 minutes.
11.5
Minutes to Recover
24
Current ACH
✅ PASSES 20-MINUTE VALIDATION RULE
Pharma & Process
💧 WFI Loop Velocity & Biofilm Preventer
Calculates exact pump LPM to maintain turbulent flow (>1.5 m/s) in sanitary tubing.
85.6
Minimum Required Flow Rate (LPM)
5.1
Cubic Meters / Hour (m³/h)
Dead-legs in the piping network MUST not exceed 1.5D to prevent stagnation.
🦠 Autoclave / SIP F0 Lethality Calc
Proves thermal sterilization cycles meet FDA 1-in-a-million SAL overkill standards.
Biological Organism Parameters
Geobacillus Stearothermophilus
15.0
Accumulated F0 Value (Mins)
Loading...
F0 ≥ 15 minutes is the universally accepted requirement for a highly robust FDA "Overkill Cycle" for terminal sterilization.
🌪️ Reactor Agitator Power Sizer
Calculates the exact motor mechanical kW required to mix API fluids in vats.
5.1 kW
Mechanical Shaft Power
7.5 kW
Min. Motor Rating (+30%)
395 Nm
Twisting Torque
Power P = Np × ρ × n³ × D⁵. Failure to add motor margin results in burnt stators during dense fluid spikes.
❄️ Lyophilizer Energetics Calc
Calculates the immense continuous energy required to freeze-dry (sublime) biological ice into vapor.
Thermodynamic Constants
8.2 kW
Continuous Heating Load (Shelf)
15.0 kW
Condenser Refrig. Load
The shelf heater provides driving energy for vapor evolution, while the -70°C condenser compressor requires vastly more energy to trap that incoming vapor under high vacuum.
🛢️ Reactor Heat/Cool Time Predictor
Estimates processing time for Jacketed API Vessels using lumped capacitance heat transfer.
Water = 4.18. Oils ~ 2.0
38
Estimated Time (Minutes)
543,400
Total Heat Energy (kJ)
ERROR: Utility temperature must be hotter than target (for heating) or colder than target (for cooling).